220.44 Receptacle Loads — Other Than Dwelling Units. So this article gives use how receptacle loads should be calculated with the understanding that there is demand factor in the mix. Here is where the code can be a little misunderstood. This code tells use to refer back to 220.14(H) and (I) and look at the table 220.42 and 220.44. To better understand how and why you must first understand that we take for granted that a convenience outlets only gets used every once and a will.
“Receptacle loads calculated in accordance with 220.14(H) and (I) shall be permitted to be made subject to the demand factors given in Table 220.42 or Table 220.44.”
Table 220.42 Lighting Load Demand Factors
Portion of Lighting Load to Which Demand Factor
Types of Occupancy
Applies (volt-Amperes)
Demand Factor(%)
Dwelling Units
First 3000
From 3001 to 120,000
Remainder over 120,000
100
35
25
Hospitals
First 50,000
Remainder over 50,000
50
40
Hotels and Motels,
Including apt. houses without provisions for cooking by tentants
First 20,000
From 20,001 to 100,000
Remainder over 100,000
50
40
30
Warehouses (storage)
First 12,500
Remainder over 12,500
100
50
All Others
Total volt-amperes
100
Table 220.44 Demand Factors for Non-Dwelling Receptacle Loads
Portion of receptacle loads to which demand factor applies
(Volt-Amperes)
Demand Factor(%)
First 10kVA or less
100
Remainder over 10kVA
50
Leave a comment